Locations
Switchgears are located anywhere that isolation and protection may be required. These locations include generators, motors, transformers, and substations.
Substations
Typically switchgear in substations is located on both the high voltage and the low voltage side of large power transformers. The switchgear located on the low voltage side of the transformers in distribution type substations, now are typically located in what is called a Power Distribution Center (PDC). Inside this building are typically smaller, medium-voltage (~15kV) circuit breakers feeding the distribution system. Also contained inside these Power Control Centers are various relays, meters, and other communication equipment allowing for intelligent control of the substation.
For industrial applications, a transformer and switchgear line-up may be combined in one housing, called a unit substation.
Housing
Switchgear for low voltages may be entirely enclosed within a building. For transmission levels of voltage (high voltages over 66 kV), often switchgear will be mounted outdoors and insulated by air, though this requires a large amount of space. Gas-insulated switchgear used for transmission-level voltages saves space, although it has a higher equipment cost.
At small substations, switches may be manually operated, but at important switching stations on the transmission network all devices have motor operators to allow for remote control.
Types
A piece of switchgear may be a simple open air isolator switch or it may be insulated by some other substance. An effective although more costly form of switchgear is "gas insulated switchgear" (GIS), where the conductors and contacts are insulated by pressurized (SF6) sulfur hexafluoride gas. Another common type is oil insulated switchgear.
Circuit breakers are a special type of switchgear that are able to interrupt fault currents. Their construction allows them to interrupt fault currents of many hundreds or thousands of amps. The quenching of the arc when the contacts open requires careful design, and falls into four types:
Oil circuit breakers rely upon vaporisation of some of the oil to blast a jet of oil through the arc.
Gas (SF6) circuit breakers sometimes stretch the arc using a magnetic field, and then rely upon the dielectric strength of the SF6 to quench the stretched arc.
Vacuum circuit breakers have minimal arcing (as there is nothing to ionise other than the contact material), so the arc quenches when it is stretched a very small amount (<2-3 mm). Vacuum circuit breakers are frequently used in modern medium-voltage switchgear to 35,000 volts. Air circuit breakers may use compressed air to blow out the arc, or alternatively, the contacts are rapidly swung into a small sealed chamber, the escaping of the displaced air thus blowing out the arc. Circuit breakers are usually able to terminate all current flow very quickly: typically between 30mS and 150mS depending upon the age and construction of the device. Several different classifications of switchgear can be made:
By size of current that they may safely switch:
Circuit breakers can open and close on fault currents
Load-break/Load-make switches can switch normal system load currents
Isolators may only be operated while the circuit is dead, or the load current is very small.
By voltage class:
Low voltage (less than 1000 volts AC)
Medium voltage (1000-35,000 volts AC)
High voltage (more than 35,000 volts AC)
By insulating medium:
Air
Gas (SF6 or mixtures)
Oil
Vacuum
By construction type:
Indoor
Outdoor
Industrial
Utility
Marine
Draw-out elements (removable without many tools)
Fixed elements (bolted fasteners)
Live-front
Dead-front
Open
Metal-enclosed
Metal-clad
Arc-resistant
By IEC degree of internal separation
No Separation (Form 1)
Busbars separated from functional units (Form 2a, 2b, 3a, 3b, 4a, 4b)
Terminals for external conductors separated from busbars (Form 2b, 3b, 4a, 4b)
Terminals for external conductors separated from functional units but not from each other (Form 3a, 3b)
Functional units separated from each other (Form 3a, 3b, 4a, 4b)
Terminals for external conductors separated from each other (Form 4a, 4b)
Terminals for external conductors separate from their associated functional unit (Form 4b)
By interrupting device:
Fuses
Air Blast Circuit Breaker
Minimum Oil Circuit Breaker
Oil Circuit Breaker
Vacuum Circuit Breaker
Gas (SF6) Circuit breaker
By operating method:
Manually-operated
Motor-operated
Solenoid/stored energy operated
By type of current:
Alternating current
Direct current
By interrupting rating (maximum short circuit current that the device can safely interrupt)
By application:
Transmission system
Distribution.
A single line-up may incorporate several different types of devices, for example, air-insulated bus, vacuum circuit breakers, and manually-operated switches may all exist in the same row of cubicles.
Ratings, design, specifications and details of switchgear are set by a multitude of standards. In North America mostly IEEE and ANSI standards are used, much of the rest of the world uses IEC standards, sometimes with local national derivatives or variations.
Functions
One of the main basic functions of switchgear is protection: discrimination between circuit breakers enhances availability, that is to say continuity of service. The overall approach is termed coordination: the standards provide a framework for discrimination and cascading that protects the integrity of the power system and minimizes the scope of downstream outages.
Safety
To help ensure safe operation sequences of switchgear, trapped key interlocking provides predefined scenarios of operation. James Harry Castell invented this technique in 1922. For example, if only one of two sources of supply are permitted to be connected at a given time, the interlock scheme may require that the first switch must be opened to release a key that will allow closing the second switch. Complex schemes are possible.
Wednesday, October 24, 2007
switch gear for substation
The term switchgear, used in association with the electric power system, or grid, refers to the combination of electrical disconnects, fuses and/or circuit breakers used to isolate electrical equipment. Switchgear is used both to de-energize equipment to allow work to be done and to clear faults downstream.
Posted by DOKUTAKE at 3:28 am
Subscribe to:
Post Comments (Atom)
3 comments:
great information
switchgear adalah sesuatu yg penting,ia perlu di selenggara dgn baik...
macam bagus je.
Post a Comment