Thursday, September 27, 2007

SUBstation of electrical



A 115 kV to 41.6/12.47 kV 5000 kVA 60 Hz substation with circuit switcher, regulators, reclosers and control building,An electrical substation is a subsidiary station of an electricity generation, transmission and distribution system where voltage is transformed from high to low or the reverse using transformers.
Explanation
Transformation may take place in several stages in sequence, starting at the generating plant where the voltage is increased for transmission purposes and is then progressively reduced to the voltage required for household or industrial use. The range of voltages in a power system varies from 110 V up to 765 kV depending on the country.
A substation that has a step-up transformer increases the voltage while decreasing the current, while a step-down transformer decreases the voltage while increasing the current for domestic and commercial distribution. The word substation comes from the days before the distribution system became a grid. The first substations were connected to only one power station where the generator was housed, and were subsidiaries of that power station.
Substations generally contain one or more transformers, and have switching, protection and control equipment. In a large substation, circuit breakers are used to interrupt any short-circuits or overload currents that may occur on the network. Smaller distribution stations may use recloser circuit breakers or fuses for protection of branch circuits. Substations do not (usually) have generators, although a power plant may have a substation nearby. A typical substation will contain line termination structures, high-voltage switchgear, one or more power transformers, low voltage switchgear, surge protection, controls, and metering. Other devices such as power factor correction capacitors and voltage regulators may also be located at a substation.
Substations may be on the surface in fenced enclosures, underground, or located in special-purpose buildings. High-rise buildings may have indoor substations. Indoor substations are usually found in urban areas to reduce the noise from the transformers, for reasons of appearance, or to protect switchgear from extreme climate or pollution conditions.
Where a substation has a fence, it must be properly grounded (UK: earthed) to protect people from high voltages that may occur during a fault in the transmission system. Earth faults at a substation can cause Earth Potential Rise at the fault location.
Transmission substation
A transmission substation is one whose main purpose is to connect together various transmission lines.
The simplest case is where all transmission lines have the same voltage. In such cases, the substation contains high-voltage switches that allow lines to be connected together or isolated for maintenance.
Transmission substations can range from simple to complex. A small "switching station" may be little more than a bus plus some circuit breakers. The largest transmission substations can cover a large area (several acres/hectares) with multiple voltage levels, and a large amount of protection and control equipment (capacitors, relays, switches, breakers, voltage and current transformers).
Distribution substation
A distribution substation is one whose main purpose is to transfer power from the transmission system to the distribution system of some area. It is uneconomical to directly connect electricity consumers to the main transmission network (unless they use large amounts of energy); so the distribution station reduces voltage to a value suitable for connection to local loads.
The input for a distribution substation is typically at least two transmission or subtransmission lines. Input voltage may be, for example, 115 kV, or whatever is common in the area. The output is a number of feeders. Distribution voltages are typically medium voltage, between 2.4 and 33 kV depending on the size of the area served and the practices of the local utility.
The feeders will then run overhead, along streets (or under streets, in a city) and eventually power the distribution transformers at or near the customer premises.
Besides transforming the voltage, the job of the distribution substation is to isolate faults in either the transmission or distribution systems. Distribution substations may also be the points of voltage regulation, although on long distribution circuits (several km/miles), voltage regulation equipment may also be installed along the line.
Complicated distribution substations can be found in the downtown areas of large cities, with high-voltage switching, and switching and backup systems on the low-voltage side. More typical distribution substations have a switch, one transformer, and minimal facilities on the low-voltage side.
Design
The main issues facing a power engineer are reliability and cost. A good design attempts to strike a balance between these two, to achieve sufficient reliability without excessive cost. The design should also allow easy expansion of the station, if required.
Layout
In the largest stations, incoming lines will almost always have a disconnect switch and a circuit breaker. In some cases, the lines will not have both; with either a switch or a circuit breaker being all that is considered necessary. These devices are used as isolation and protection devices. A disconnect switch is almost always used solely to provide isolation, due to it not being rated for breaking a loaded circuit, whilst a circuit breaker is often used both as an isolation element as well as a protection device.[clarify] Where a large fault current flows through the circuit break this may be detected through the use of current transformers. The magnitude of the current transformer outputs may be used to 'trip' the circuit breaker resulting in a disconnection of the load supplied by the circuit break from the feeding point. This seeks to isolate the fault point from the rest of the system, and allow the system to continue operating with minimal impact.
Once past the switching components, the lines of a given voltage all tie in to a common bus. This is a number of thick metal bus bars, in most cases there are three bars, since three-phase electrical power distribution is largely universal around the world.
Substations that require additional reliability often have a double bus or even a double ring bus, in which the bus system is actually duplicated, with each feeder (and all or most outgoers) having a connection to each separate bus. Most substations will not have this, as it is mainly for reliability in substations whose failure would bring down a substantial part of the system, or whose load is of vital importance. Other compromises between a single and double bus can be found; for example, the breaker-and-a-half setup.
Once having established buses for the various voltage levels, transformers may be connected between the voltage levels. These will again have a circuit breaker, much like transmission lines, in case a transformer has a fault (commonly called a 'short circuit').
Along with this, a substation always has control circuitry needed to command the various breakers to open in case of the failure of some component.
Switching function
An important function performed by a substation is switching, which is the connecting and disconnecting of transmission lines or other components to and from the system. Switching events may be "planned" or "unplanned".
A transmission line or other component may need to be deenergized for maintenance or for new construction; for example, adding or removing a transmission line or a transformer.
To maintain reliability of supply, no company ever brings down its whole system for maintenance. All work to be performed, from routine testing to adding entirely new substations, must be done while keeping the whole system running.
Perhaps more importantly, a fault may develop in a transmission line or any other component. Some examples of this: a line is hit by lightning and develops an arc, or a tower is blown down by a high wind. The function of the substation is to isolate the faulted portion of the system in the shortest possible time.
There are two main reasons: a fault tends to cause equipment damage; and it tends to destabilize the whole system. For example, a transmission line left in a faulted condition will eventually burn down, and similarly, a transformer left in a faulted condition will eventually blow up. While these are happening, the power drain makes the system more unstable. Disconnecting the faulted component, quickly, tends to minimize both of these problems.

Electric power supply


Acme Electric is a full line manufacturer of low voltage (600 V and below) dry type distribution transformers using both copper and aluminum conductor, offering an array of products between 0.250-1000 KVA. Acme's product offering covers the full spectrum of applications, from commercial general power distribution and high harmonic conditions to specific industrial motor drive/factory automation systems, to low voltage landscape lighting applications. All Acme products are designed, constructed and rated to meet or exceed the standards established by UL, CSA, CE, NEMA, ANSI and IEEE.